Counterflow

A two-way connect creates two links, one in each direction. When agents use such a connection in both directions, the two links share one door. The setting counterflow of NetworkSimulation decides how much the door passes in total and how it splits the passages between the two directions. The default is "bounding".

The SFPE hydraulic model has no counterflow term. The 6th edition chapter mentions counterflow only through one entry in its reference list [1, ref. 57, p. 2199]. The rule on this page is therefore an extension of this model. It is calibrated on walkway and stair data, not validated (Limitations).

Choose a setting

NetworkSimulation(network, populations, counterflow="bounding")
counterflowTotal of both directions while both queueSplitCarry
"bounding" (default)0.84–0.94 C (doors, openings), 0.75–0.94 C (stairs)by queue share, at least 17 % per directionone for the pair
"estimate"0.90–1.00 C (doors, openings), 0.80–1.00 C (stairs)by queue share, at least 17 % per directionone for the pair
"independent"2 C: each link keeps its full capacitynoneone per link

$C = F_s\,(w - 2b)$ is the one-way capacity of each link of the pair in persons/s. Any other value raises ValueError. The constants are private (simulation._COUNTERFLOW); there is no public way to change them.

"independent" is the behaviour of versions before this rule. Under "estimate" a door used 50/50 passes $C/2$ each way. Under "bounding" it passes $0.47\,C$ each way.

When it acts

  • Pairs. The two links created by one connect(..., bidirectional=True) call form a pair. A connection into a safe node creates one link and no pair. Two one-way connect calls between the same nodes are two doors, each with its full $C$.
  • Active steps. A pair is in counterflow in a step when both of its links have a queue. There is no smoothing and no memory of earlier steps, apart from the carry.
  • The carry is always shared. Under "bounding" and "estimate" the pair holds one carry, even when only one direction queues. A passage in one direction uses credit the other direction would have had.
  • Default routing never uses a link both ways. Without target, every shortest route moves closer to a safe node, or as close over fewer links, so no agent walks a link against another (Verification, chain row). Counterflow arises only when populations have different targets.

A run gives the same result under all three values unless some pair is in counterflow in some step or passes agents in both directions at any time. The second case can matter. Take two 200 m² rooms A and B joined by one two-way 1 m door of length 0 ($C\,\Delta t = 0.455$), each with an exit of length 0. One agent in A heads for B’s exit at once. One agent in B heads for A’s exit after a pre-movement time of 0.5 s. The two queues never exist together.

counterflowExit times
"independent"1.0 s and 1.5 s
"estimate", "bounding"1.0 s and 2.0 s

The first passage leaves a carry of $1.455 - 1 = 0.455$. One step later the budget is $0.455 + 0.455 = 0.91 < 1$, so the second agent passes one step later than with its own carry.

The rule

The rule runs inside stage 4 of the update scheme (code: simulation._Run._pair_state, _trim_pairs, _pair_excess, _update_carry, _update_pair_time; pairing in network.Network.connect).

SymbolMeaningUnit
$\ell$, $\bar\ell$the two links of one pair–
$C$one-way capacity of each link, $F_s(w - 2b)$persons/s
$n_\ell$agents queued at $\ell$ in this step, after walking–
$s_\ell = n_\ell/(n_\ell + n_{\bar\ell})$queue share of $\ell$–
$s = \min(s_\ell, s_{\bar\ell})$minor share, in $(0, \tfrac12]$–
$g(s)$two-way total in units of $C$–
$y_\ell$pass share of $\ell$; $y_0$ its minimum–
$c_P$, $B_P$pair carry and pair budgetagents
$\sigma_\ell$, $\lambda$pair counter of $\ell$ and pair key–
$j$place of a candidate among this step’s candidates on its own link, $0, 1, \ldots$–
$\tilde C_\ell$effective capacity of $\ell$ in the supply limitpersons/s

Shares count agents (heads), not area factors.

Total and split. In an active step

$$ g(s) = g_0 + (g_{1/2} - g_0)\,2s , $$$$ y_\ell = y_0 + (1 - 2y_0)\,s_\ell , $$$$ y_{\bar\ell} = 1 - y_\ell . $$

$g$ is a linear interpolation between two anchors, $g_0$ at a vanishing minor share and $g_{1/2}$ at balance. It is a choice of this model, not a fitted law.

Budget. The pair has one budget per step:

$$ B_P = c_P + g(s)\,C\,\Delta t \quad\text{(active)}, $$$$ B_P = c_P + C\,\Delta t \quad\text{(otherwise)} . $$

At most $\lfloor B_P \rfloor$ agents pass the pair in the step, in both directions together.

Order inside stage 4.

  1. Each direction offers its first $\lfloor B_P \rfloor$ queued agents.
  2. The target nodes admit them as before: free space, supply and merge key.
  3. For each active pair, the first $\lfloor B_P \rfloor$ admitted agents in order of the pair key pass: $$ \lambda = \sigma_\ell + \frac{j + 1}{y_\ell} . $$ Equal keys go to the link that connect created first, without a random draw. The other agents stay queued.
  4. The node carry $\gamma_n$ is updated with the passages that remain, so the allowance of a trimmed agent stays in $\gamma_n$ up to its cap.
  5. In an active pair $\sigma_\ell$ grows by $q_\ell / y_\ell$, where $q_\ell$ agents passed $\ell$. Otherwise $\sigma_\ell = 0$, so each counterflow episode starts fresh.

Carry. After the step the pair keeps

$$ c_P = \operatorname{clip}\bigl(B_P - q_\ell - q_{\bar\ell},\ 0,\ 1\bigr), $$

starting at $c_P = 1$. Under "independent" each link keeps its own carry. Since $g \le 1$, a pair passes at most $1 + C\,t$ agents in any interval $t$, in both directions together. Under "independent" each link passes up to $1 + C\,t$, the pair up to $2 + 2C\,t$.

Supply. In an active step the link enters the supply limit of its target node with its share of the door,

$$ \tilde C_\ell = y_\ell\,g(s)\,C , $$

and with $\tilde C_\ell = C$ otherwise. Since $\tilde C_\ell \ge y_0\,g_0\,C > 0$, a link with a queue always counts.

Presets and their sources

counterflow$y_0$$g_0 \to g_{1/2}$, door and opening$g_0 \to g_{1/2}$, stair
"bounding"0.170.84 → 0.940.75 → 0.94
"estimate"0.170.90 → 1.000.80 → 1.00

Stair entries (kind="stair") use the stair values; doors and openings use the door values. The anchors are calibration choices, not validation.

ValueSourceNote
$y_0 = 0.17$Navin and Wheeler: a stream with $V$ % of the flow takes $Y = 17 + 0.64\,V$ % of the width, on 7–8 ft sidewalks [21, p. 36; Fig. 1, p. 31]Adapted: used as a share of passages, not of width, with slope $1 - 2y_0 = 0.66$ so that $y_\ell + y_{\bar\ell} = 1$
door $g_{1/2} = 0.94$ (bounding)maxima of 24.7 (two-way) and 26.2 (one-way) persons/ft/min, ratio 0.94 [22, p. 4]; 0.94 at 180° [28, Fig. 6]lowest balanced walkway total; ratio our arithmetic
door $g_0 = 0.84$ (bounding)loss of 14.5, 11.5, 8.5, 6.0, 4.0 % at minor share 0.1–0.5, i.e. $g$ = 0.855–0.96 [21, Table III, p. 36]; “capacity reductions of about 15 percent” at 90/10 [31, p. 11-7]$0.84 + 0.2\,s$ lies at or below Navin and Wheeler for $s$ = 0.2–0.5 and 0.005 above at $s = 0.1$
door $g_{1/2} = 1.00$ (estimate)“pedestrians equally share the width” [24, p. 1613]; two-way about equal to one-way at 50/50 [23, p. 44]between walkways (0.94–0.96) and Arnott’s door (1.05–1.14)
door $g_0 = 0.90$ (estimate)gives $g(0.1) = 0.92$, close to the middle (0.91) of the walkway range 0.84–0.98 at $s \approx 0.1$0.98 is Wong et al.’s model at $s \approx 0.1$ [28, Eq. 1], our computation
stair $g_0 = 0.75$ (bounding)Tofiło et al.’s recommendation [29, p. 520]. Their single runs on one 1.15 m stair give 0.75 (Fig. 6, flow, read by eye) to 0.78 (Table 4, last-out time) [29, Fig. 6, p. 520; Table 4, p. 515]a fraction of the no-counterflow flow, not of capacity; corroborated by Cheung and Lam’s about 25 % stair loss [24, Fig. 3, p. 1615]
stair $g_0 = 0.80$ (estimate)17–19 % flow reduction at 1–2 persons/m², read by eye [29, Fig. 6, p. 520]; 20–27 % [24, Fig. 3, p. 1615]–
stair $g_{1/2}$ = 0.94 / 1.000.94 borrowed from walkways (no stair total at balance); 1.00: loss about 0 at 50/50 [24, Fig. 3, p. 1615]–

Whether Navin and Wheeler’s 17 % width intercept carries over to a minimum share of passages is open.

Evidence

$g$ is the two-way total divided by a one-way value. The baseline matters. Only Arnott et al.’s door can be stated against this model’s $C = F_s(w - 2b)$; the other studies divide by their own measured one-way flow or capacity.

Evidence by facility
FacilityValueBaselineSource
Walkway, balanced$g \approx$ 0.94–1.0: 0.96; 0.94; about 1; “little reduction”; 0.94measured one-way[21, Table III, p. 36; 22, p. 4; 24, p. 1613; 31, p. 11-7; 28, Fig. 6]
Walkway, minor share about 0.1$g \approx$ 0.84–0.86; or 0.98 from Wong et al.’s model (our computation). Not establishedmeasured one-way[21, Table III, p. 36; 31, p. 11-7; 24, p. 1616; 28, Eq. 1]
Door 1.72 m, about 50/500.97 and 1.05 persons/s per direction: 1.05–1.14 × the SFPE half of 0.92 persons/s (our arithmetic), 1.15–1.25 × half the measured one-way flow of 1.56–1.79 persons/sSFPE $C$ and measured one-way[6, pp. 5–6; Table 1, p. 10]
Stairsminor-direction capacity 53/67 = 0.79 ascending and 60/78 = 0.77 descending at flow ratio 0.1 (our arithmetic); about 25 % loss as the minor share → 0measured one-way capacity[27, Observation Results, Figs. 2a–b; 24, Fig. 3, p. 1615]
Firefighters ascending a stair5 firefighters against 73 descending students on 1.15 m flights: flow reduction 3–25 %, one run per density; evacuees moved “considerably faster” than in real evacuations; speeds 0.83–0.97 of free speed in the same experimentmeasured flow without counterflow[29, pp. 518, 520; 30, Table 7, p. 38]
Design rulesnarrow stairs: a minor flow can “cut … in half” the capacity; lanes of at least 30 innone (no data)[23, pp. 61, 79, 160]
Corridors, other0.75 from Voronoi fundamental diagrams, not a cross-section flow; 1.43 against an unsaturated one-way baseline (our arithmetic)measured one-way[32, §4.1, Fig. 9b; 33, pp. 7–8]
  • No study measures a door away from a 50/50 split. Every door value below 50/50 is borrowed from walkways.
  • Stairs lose more to opposing flow than walkways.
  • Arnott et al. took the flows “only … while people were moving in both directions” [6, p. 5]. All data come from non-emergency movement or trials.
  • $g = 2$ ("independent") lies above every value in the table.

Candidate forms

Seven forms were compared before the rule was chosen.

FormRuleEvidence (baseline)LimitsIn the code
M0$C$ each way, $g = 2$none; above all dataa door passes twice its capacity"independent"
M1$C/2$ each way while both are activeArnott’s door at about 50/50: 5–14 % conservative against the SFPE half [6, p. 6]; EvacuatioNZ v2.14 as reported by Arnott et al. [6, p. 8]; “cut … in half” for narrow stairs, a design rule [23, pp. 61, 160]at $s \approx 0.1$ caps the major stream at $0.5\,C$ against about 0.77–0.80 C in walkway data; jumps at the first opposing agentnot offered; "estimate" equals it at $s = \tfrac12$
M2shared $C$ split by demand, $g = 1$[24, Eqs. 3–4, p. 1613; 25, p. 184; 23, p. 44]; 0.96 [21, Table III, p. 36]no minor-stream penalty; a small group waits behind almost the whole opposing queuespecial case of the rule ($y_0 = 0$, $g \equiv 1$); not offered
M3shared $g(s)\,C$ split by demand$g(s)$ from [21, Table III; 24, Eqs. 7, 9; 26, Tables 3–4; 28, Eq. 1; 35, Eqs. 8–14, pp. 22–24]every $s$-dependent $g$ comes from walkways; on a door it is extrapolationbasis of the rule
M4lanes, $\lfloor w_\text{eff}/w_\text{lane} \rfloor$, at least one per directionlane counts [21, pp. 32, 36; 34, p. 38]; lane design [23, p. 160]no capacity validation; lane width 0.5–0.76 m across sourcesnot implemented; its minimum share enters as $y_0$
M5alternation on single-lane linksnone; Pathfinder’s SFPE mode exchanges queues as a model rule [36]–not implemented
M6stair minus one lane while the minor stream is present$w_\text{lane} \ge 30$ in, a design rule [23, p. 79]; 75 % recommendation [29, p. 520]the lane rule leaves 0.34 of a 1.15 m stair to the major stream (a 66 % loss) against at most 25 % measured on that stair (our arithmetic, one experiment)Tofiło et al.’s value enters as stair $g_0 = 0.75$; the lane form is documented only

The rule follows M3 with a shared door. One shared carry keeps the pair within $1 + C\,t$, so a sparse opposing stream cannot pass on credit left idle on its own link. The rule contains M1 and M2 as special cases. At 50/50, "estimate" gives the halving that Arnott et al. report for EvacuatioNZ v2.14.

Width form

Arnott et al. describe the halving as “half of the door width is taken as the clear width”, but their arithmetic is $(w - 2b)/2$: 0.92 persons/s for the 1.72 m door [6, p. 6]. With $F_s = 1.3$ persons/s/m and $b = 0.15$ m (our arithmetic):

Door$F_s(w - 2b)/2$$F_s(w/2 - 2b)$Measured per direction
1 m0.455 persons/s0.26 persons/s–
1.72 m0.923 persons/s0.728 persons/s0.97–1.05 persons/s [6, p. 6]

This model works on $C$, so its halving equivalent is $C/2 = F_s(w - 2b)/2$. No source measures a gap between opposing streams. The published sources do not state when EvacuatioNZ v2.14 applies its rule or how it forms the half width.

Bounding or estimate

Gwynne et al. define bounding defaults as “derived from relevant empirical data” [11, pp. 335–336], not from extreme outliers [11, p. 343]. They also allow values from “codes and standards, or common practice” [11, p. 342]. "bounding" follows the first sense: its door values lie at the low end of the walkway data, and its stair $g_0$ is Tofiło et al.’s recommendation. M1 would follow the second (EvacuatioNZ, Fruin). The default is "bounding"; "estimate" takes the centre of the data.

  • The bound holds while both directions keep a queue. When the minor stream is sparse, its queue is empty in some steps, the loss is not charged then, and the realised total is higher, above Navin and Wheeler’s 0.855 near $s = 0.1$.
  • For doors at 50/50, "bounding" lies 10–18 % below the only door measurement (0.94 against 1.05–1.14).
  • The other defaults of this model are design values, so the default set is mixed. Gwynne et al. ask: “Is this default ‘scenario’ conservative, optimal or somewhere in between?” [11, p. 342] (Limitations).

Neither preset bounds the evacuation time or the realised two-way flow in every case.

What it changes

Runs where populations with different targets use a two-way connection in both directions become slower by default than with "independent". The tests show two cases (Verification).

  • 36 against 4 at a 1 m door. Under "bounding" the 4 agents of the minor stream pass at 4.0, 9.0, 15.5 and 22.0 s, 5.0–6.5 s apart, instead of waiting for the whole opposing queue. The last passage of the major stream moves from 38.5 s ("independent") to 46.5 s.
  • Responders on a stair. 4 responders enter a 1.2 m stair entry against 20 evacuees leaving it. The responders are out by 20.5 s ("bounding") or 19.5 s ("estimate") instead of 4.5 s. The evacuees’ clearance rises from 21.5 s to 30.0 s or 29.0 s.

Not modelled

  • Counterflow inside nodes: corridors and stair flights keep the speed $k(1 - aD)$ with all agents counted, whatever their direction.
  • There is no counterflow output (issue #40).

See Limitations.